
|
|
|
|
USP <797> vs. Turbulent (nonunidirectional flow) Isolators
Date:
The views expressed herein are the personal views of Air
Safe, LLC. and not necessarily those of the compounding pharmacy industry,
isolator manufacturer’s or those of any other individual or entity.
I am sure you are aware the revised USP <797> becomes
effective on June 1st this year. The
revised document has some specific details concerning the usage of compounding
isolators I feel obligated to inform you about.
We have also collected field data on a number of different isolators
located in many hospital pharmacies and will share that data with you as well.
First let me state the section of the USP <797> which
may be of concern to you and then my professional response.
HAZARDOUS DRUG MANIPULATIONS
Excerpt from page 14 of <797>
The ISO Class 5 (see Table 1) BSC or CACI shall be placed in
an ISO Class 7 (see Table 1) area that is physically separated (i.e., a
different area from other preparation areas) and optimally has not less than 0.01-inch
water column negative pressure to adjacent positive pressure ISO Class 7 (see
Table 1) or better ante-areas, thus providing inward airflow to contain any
airborne drug. A pressure indicator shall be installed that can be readily
monitored for correct room pressurization. The BSC and CACI optimally should be
100% vented to the outside air through HEPA filtration.
If a CACI that meets the requirements of this chapter is
used outside of a buffer area, the compounding area shall maintain a minimum
negative pressure of 0.01-inch water column and have a minimum of 12 ACPHs.
When closed-system vial-transfer devices (CSTDs) (i.e., vial-transfer
systems that allow no venting or exposure of hazardous substance to the
environment) are used, they shall be used within the ISO Class 5 (see Table 1) environment
of a BSC or CACI. In facilities that prepare a low volume of hazardous drugs,
the use of two tiers of containment
(e.g., CSTD within a BSC or CACI that is located in a non-negative
pressure room) is acceptable.
My condensed interpretation is: If you use a containment isolator and it
meets the USP requirements and you only perform low volumes of hazardous drugs
you can utilize the isolator in an area without the negative pressure
requirement; however the 12 air changes per hour still apply. If this is not your situation, you should
look into installing environmental controls to comply with the above excerpt.
HAZARDOUS DRUG STORAGE
Excerpt from pages 13-14 of <797>
Many hazardous drugs have sufficient vapor pressures that
allow volatilization at room temperature; thus storage is preferably within a
containment area such as a negative pressure room. The storage area should have
sufficient general exhaust ventilation, at least 12 air changes per hour (ACPH)4
to dilute and remove any airborne contaminants.
My interpretation is:
Hazardous drugs may be stored in your negative pressure chemo room with
your isolator or BSC. You must have a
minimum of 12 ACH, so your drug storage area(s) should be monitored for air
change rates.
AIR FLOW REQUIREMENTS FOR THE CRITICAL AREAS (ISO CLASS 5)
Excerpt from page 21 of <797>
HEPA-filtered air shall be supplied in critical areas (ISO
Class 5, see Table 1) at a velocity sufficient to sweep particles away from the
compounding area and maintain unidirectional airflow during operations. Proper
design and control prevents turbulence and stagnant air in the critical area. In
situ air pattern analysis via smoke studies shall be conducted at the critical
area to demonstrate unidirectional airflow and sweeping action over and away
from the product under dynamic conditions.
My interpretation is:
If you use a compounding isolator it must utilize uni-directional
airflow within the critical area. Turbulent
airflow within the critical areas is not acceptable concerning the requirements
of the USP <797>.
You can determine if your isolator is a turbulent flow unit
or a unidirectional unit by calling the manufacturer, us or by looking at the
supply HEPA filter set up within the critical area of the isolator.
PLACEMENT OF COMPOUNDING ISOLATORS
Excerpt from pages 21-22 of <797>
CAIs and CACIs shall be placed in an ISO Class 7 (see Table 1)
buffer area unless they meet all of the following conditions:
• The
isolator shall provide isolation from the room and maintain ISO Class 5 (see
Table 1) during dynamic operating conditions, including transferring
ingredients, components, and devices into and out of the isolator and during
preparation of CSPs.
• Particle
counts sampled approximately 6 to 12 inches upstream of the critical exposure
site shall maintain ISO Class 5 (see Table 1) levels during compounding
operations.
• Not more
than 3520 particles (0.5 um and larger) per m3 shall be counted during material
transfer, with the particle counter probe located as near to the transfer door
as possible without obstructing the transfer.8
Our field testing data supports that isolators located
outside of a buffer area (ISO Class 7) which utilized unidirectional flow for
the critical areas meet these requirements.
Isolators we have tested which utilize turbulent flow in the critical
areas have been problematic at best in meeting these requirements.
RECOVERY TIMES FOR ISOLATORS
Excerpt from page 23 of <797>
When isolators are used for sterile compounding, the
recovery time to achieve ISO Class 5 (see Table 1) air quality shall be
documented and internal procedures developed to ensure that adequate recovery
time is allowed after material transfer before and during compounding
operations.
Our field testing data show that isolators which utilize
unidirectional airflow in the critical areas recover from a simulated breach† typically
in less than one minute and we have yet to see one not recover within three
minutes.
Our field testing on turbulent flow isolators show
dramatically different results. In most
cases the turbulent flow isolator does not recovery to an ISO class 5
environment even after 30 minutes. In
many field tests we have stopped the recovery test due to time constraints and
after 15 minutes we are still measuring over 28,000 particles per cubic meter. (An ISO Class 5 requires no more than 3,520
particles per cubic meter.)
Based on our field testing of the recovery periods for
various isolators we recommend no less than a one hour wait (purge) time after
any material transfer into or out of an isolator which utilizes turbulent flow in
its critical space.
† This test is
performed in accordance with the CETA Compounding Isolator Testing Guide: CAG-002-2006; section 2.07.
VIABLE SAMPLING
Excerpt from page 25 of <797>
Air sampling shall be performed at least semiannually i.e.,
every 6 months) as part of the re-certification of facilities and equipment. If
compounding occurs in multiple locations within an institution (e.g., main
pharmacy, satellites), environmental sampling is required for each individual
compounding area.
You should be performing viable sampling in all critical
areas (hood/isolators) and the buffer rooms.
Active air sampling is required, settling plates are not sufficient. We can provide this sampling and reporting
for you if you are not already doing this in house.
I hope this information is helpful to you in verifying your
compliance with the USP <797> document.
If you should have any questions, please do not hesitate to give me a
call anytime.
Sincerely,
Michael D. Alleman
President
Air Safe, LLC. 888-924-7723
|





